Pilz 774610 PNOZ XV3.1 Safety Relay 24-240 V AC/DC in Navi Mumbai
Order the Pilz PNOZ XV3.1 safety relay, article number 774610, from Indus MegaMart for your Navi Mumbai maintenance or machine-building requirements. This standalone, hardwired relay combines a 24–240 V AC/DC supply with three instantaneous normally open safety contacts, two time-delayed normally open safety contacts, and one normally closed auxiliary contact. Its twelve release-delay settings span 0.1 to 30 seconds, making the exact variant relevant when an engineered emergency-stop or guard-monitoring circuit calls for immediate and delayed interruption.
Price, stock and ordering in Navi Mumbai
Open the product listing to see the current GST-inclusive price and available quantity. Pilz specifies one device per manufacturer packaging unit; confirm the Indus MegaMart selling quantity before ordering. Enter the delivery pincode for your Navi Mumbai plant, workshop or project site and check the applicable delivery information. Purchase invoices contain the company GST number.
Buy Now – Pilz PNOZ XV3.1 (774610)
Technical specifications of Pilz 774610
|
Parameter |
Specification |
|
Brand/model / MPN |
Pilz / PNOZ XV3.1 / 774610 |
|
GTIN |
4046548010640 |
|
Supply (UB) |
24–240 V AC/DC; AC 50–60 Hz; tolerance −15%/+10% |
|
Power consumption |
8.5 VA AC; 5 W DC |
|
Inputs/start |
2 inputs; single- or dual-channel; automatic or monitored start |
|
Input/start/feedback voltage |
24 V DC for these circuits; not the wide-range supply rating |
|
Instantaneous safety contacts |
3 NO |
|
Delayed safety contacts |
2 NO, delay-on de-energisation |
|
Auxiliary contact |
1 NC, instantaneous; not for safety circuits |
|
Semiconductor outputs |
None |
|
Selectable release delay |
0.1, 0.5, 1, 2, 4, 6, 8, 10, 15, 20, 25 or 30 s |
|
Delay accuracy/repeatability |
−15% / +15% + 50 ms; 2% repetition accuracy |
|
Safety contact ratings (both groups) |
AC-1: 8 A at 240 V AC; DC-1: 8 A at 24 V DC; AC-15: 5 A at 230 V AC; DC-13: 7 A at 24 V DC (6 cycles/min). Apply manual load and simultaneous-contact limits. |
|
Connection/mounting |
Fixed screw terminals; 35 mm DIN rail |
|
Dimensions (H × W × D) |
87 × 90 × 121 mm |
|
Net weight |
520 g |
|
Operating environment |
−10 to +55 °C; no condensation; housing IP40, terminals IP20, cabinet at least IP54 |
|
OEM packaging |
1 device per manufacturer packaging unit |
How the instantaneous and delayed contacts differ
When the monitored safety input opens, the three instantaneous safety contacts open without an intentional release delay. The two timed contacts open after the selected interval. The auxiliary NC contact can report status but must not be used to implement a safety function. The timing is not an on-delay or an ordinary process timer. Under a fault, the delayed contacts may open earlier than expected; the maximum opening time must be assessed using the specified tolerance.
Safety performance depends on the output group and delay
|
Contact group |
OEM safety characteristic |
|
Instantaneous safety contacts |
PL e / Category 4 / SIL 3 |
|
Delayed safety contacts, setting below 30 s |
PL d / Category 3 / SIL 3 |
|
Delayed safety contacts, setting 30 s or higher |
PL c / Category 1 / SIL 1 (774610 maximum is 30 s) |
These are component characteristics under the manufacturer’s conditions, not a declaration of the achieved machine safety level. A competent safety engineer must validate the whole safety function, including stop time, load, service-life limits and the required performance level.
Application and replacement selection
The 774610 is intended for emergency-stop and safety-gate monitoring. For example, a machine builder may need both immediate interruption and a delayed interruption in a validated controlled-stop arrangement. The relay supplies the contact functions; it does not itself verify that motion has stopped, control a drive’s braking sequence or justify extending hazardous operation. The applicable stop category is determined by the machine risk assessment.
When replacing a relay in a Navi Mumbai control panel, check the existing nameplate, supply type, required release time, terminal arrangement, number of immediate and delayed contacts, and required load ratings. Single-channel wiring does not provide redundant inputs; dual-channel fault detection depends on the selected wiring and OEM conditions. Prevent unexpected restart and use the required feedback and protective measures. Installation and commissioning must be performed by qualified personnel according to the Pilz operating manual.
Compare the XV3.1 order numbers before buying
|
Order number |
Nominal supply |
Selectable maximum delay |
|
774610 |
24–240 V AC/DC |
30 s |
|
774612 |
24–240 V AC/DC |
3 s |
|
774618 |
24–240 V AC/DC |
300 s |
|
774530 |
24 V DC |
30 s |
The similar model names do not establish interchangeability. Confirm the required delay setting and safety category rather than substituting solely by housing appearance. For other options, browse the Pilz range or safety relay category.
Explore Pilz products
Compare safety relays
Electrical & industrial automation
Delivery and procurement support
The standard Indus MegaMart ordering policy allows payment and orders regardless of available stock. Its standard delivery window is within 7 days when the requested quantity is covered by available stock, and within 7–14 days when it exceeds available stock or stock is zero. Confirm the actual delivery commitment for this product and your Navi Mumbai pincode before paying, particularly when planning a shutdown; the product listing may display different lead times. For multiple relays, verify the order quantity, seller pack, invoice details and applicable return or warranty terms with the seller before committing.
Frequently asked questions
1. Is 774610 a 30-second or 3-second relay?
774610 is the 30-second maximum variant. Its twelve discrete release settings begin at 0.1 s. The wide-voltage 3-second variant is 774612; match the complete order number before purchasing.
2. Can the NC contact be used as an additional safety output?
No. It is an auxiliary status contact, not a safety contact. The five normally open safety contacts consist of three immediate and two delayed outputs.
3. Can this relay delay the start of a machine?
Its adjustable timing is a release delay, not a configurable start-delay function. Reset and restart must follow the validated circuit design; automatic starting needs measures to prevent unexpected restart.
4. Does the 30-second setting have the same safety rating as shorter delays?
No. Pilz lists PL d, Category 3, SIL 3 for delayed contacts below 30 s, and PL c, Category 1, SIL 1 for delayed contacts at 30 s or longer. The instantaneous group is rated PL e, Category 4, SIL 3 under the manual’s conditions. The complete machine safety function must be assessed separately.
5. Can I use 230 V AC supply with 774610?
Yes, 230 V AC is within its nominal 24–240 V AC/DC supply range. The input, start and feedback circuits are 24 V DC; check insulation, earthing and installation requirements in the exact manual.
6. How do I check the price, selling quantity and delivery in Navi Mumbai?
Open the exact 774610 listing, review the GST-inclusive price, confirm how many devices are included in the selling unit, and check your destination pincode and required quantity before payment. For scheduled maintenance or bulk orders, confirm the applicable delivery commitment.
7. Can I order if the available quantity is insufficient?
Indus MegaMart accepts orders and payments even when the requested quantity exceeds available stock, including zero stock. Confirm the delivery commitment for your Navi Mumbai order before payment.
Order Pilz 774610 for Navi Mumbai
Confirm the 30-second maximum release-delay variant and your required selling quantity, then view the current offer and delivery details on the exact product listing.