Pilz PNOZ e1p 774130 Safety Relay 24V DC in Haora
For a Haora machine-safety replacement or new control-panel build, buy the Pilz PNOZ e1p 24VDC 2so electronic safety relay (part 774130) through its exact Indus MegaMart product listing. This standalone PNOZ e1p relay provides two instantaneous semiconductor safety outputs, supports emergency-stop and safety-gate monitoring, and fits a narrow 22.5 mm DIN-rail space. Confirm the full model number and the required output technology before purchasing; it is not a three-contact electromechanical safety relay.
Order the exact PNOZ e1p 774130 for Haora
Review the current price, GST presentation, listed selling unit and quantity on the product offer before proceeding. If you are replacing an installed relay, compare the part label, 24 V DC input supply, plug-in screw terminal arrangement and wiring requirements. Check the serviceability of your delivery PIN code through the ordering process.
View Pilz 774130 price and purchase details.
What the Pilz PNOZ e1p does
The PNOZ e1p monitors one- or two-channel safety inputs, such as emergency-stop pushbuttons and safety-gate switches. Depending on the prescribed wiring, it supports detection of shorts across contacts, automatic or monitored start, and monitoring of downstream feedback contacts. Its two semiconductor safety outputs are independent of the auxiliary status output: the auxiliary Y32 channel must not be treated as an additional safety output.
Verified technical specifications
|
Product attribute |
Detail |
|
Brand / exact part |
Pilz PNOZ e1p 24VDC 2so; article 774130 |
|
Product family |
PNOZelog standalone electronic safety relay |
|
GTIN / EAN |
4046548011999 |
|
Supply voltage |
24 V DC (not 24 V AC/DC) |
|
Safety outputs |
2 instantaneous semiconductor safety outputs, terminals 14 and 24 |
|
Other outputs |
1 auxiliary semiconductor output Y32 for status only; 2 test-pulse outputs |
|
Sensor circuit |
Single- or dual-channel input wiring; optional shorts-across-contacts detection per configuration |
|
Start / restart |
Automatic or monitored start; feedback monitoring integrated with start circuit |
|
Typical monitoring |
Emergency-stop buttons, safety gates and qualifying light-grid/safety switches |
|
Terminal type |
Plug-in screw terminals; do not confuse with spring-clamp variant 784130 |
|
DIN-rail mounting |
35 mm rail; compatible control cabinet enclosure required |
|
Overall dimensions (H × W × D) |
90.5 × 22.5 × 121 mm per exact Pilz product |
|
Net weight / OEM gross weight |
120 g / 135 g |
|
Ambient temperature |
−10 to +55 °C |
|
Housing / terminal IP |
IP40 enclosure / IP20 terminals per operating manual |
|
Cabinet installation |
Fit in suitable control cabinet; manual specifies cabinet protection at least IP54 |
|
Manufacturer product lifecycle |
Pilz catalog labels part 774130 a phase-out article; check sourcing status |
|
Manufacturer packing quantity |
1 at OEM; NOT proof of Indus MegaMart sale unit or MOQ |
|
Accessory example |
Pilz optional PNOZ X screw-terminal spares 374280; do not assume included |
Check compatibility and replacement details
Semiconductor safety outputs versus relay contacts
The two safety outputs at terminals 14 and 24 use semiconductor switching rather than conventional dry relay contacts. Other nearby Pilz PNOZ models may instead provide positively guided N/O contacts. Check the load, sensor wiring and controlled equipment against the current PNOZ e1p operating instructions before selecting a replacement. The two test-pulse outputs are provided for diagnostic functions; they are not extra safety switching outputs.
Start, wiring and enclosure conditions
Automatic start and monitored manual start require the correct start-circuit wiring. Use an arrangement appropriate to the machine risk assessment, including feedback monitoring where needed. Pilz specifies installation on a 35 mm DIN rail within a suitable control cabinet; its operating manual calls for a cabinet protection rating of at least IP54. Only competent personnel should install and validate the safety function.
Check phase-out status and terminal variant
Pilz identifies 774130 as a phase-out article. That classification makes exact-model checking especially important for maintenance procurement. Part 774130 uses plug-in screw terminals, while the related 784130 variant uses spring-loaded terminals. Do not assume that a different model or later-generation relay is a direct substitute without confirming the full circuit requirements.
Suitable industrial applications
This relay is used in machine guarding arrangements such as emergency-stop circuits, safety-gate monitoring and suitable light-grid input functions. Its correct use depends on the type of sensor, short-circuit detection, start arrangement, electrical loading and the overall engineered safety architecture. A component certificate does not by itself establish the achieved safety rating of a complete machine.
Ordering and delivery for Haora
Indus MegaMart accepts orders and payment even when the requested quantity exceeds available stock, including zero-stock orders. Its stated policy provides delivery within 7 days when the ordered quantity is within available stock, and within 7–14 days when the quantity exceeds available stock, including zero available stock. Check the current item listing and your delivery PIN code when buying. These terms do not indicate a dedicated Haora warehouse or guaranteed local inventory.
Frequently asked questions
1. Is Pilz 774130 a standalone device or an expansion module?
It is a standalone PNOZelog electronic safety relay. It does not require a myPNOZ or PNOZmulti head module to operate.
2. Does 774130 operate on 24 V DC or 24 V AC?
Pilz specifies 24 V DC for article 774130. Do not substitute a 24 V AC-only device without checking the complete circuit.
3. Are the two safety outputs relay contacts?
No. They are electronic semiconductor safety outputs. The additional Y32 output is an auxiliary signal and must not be used as a safety output.
4. Why do some catalogues say the module has five outputs?
Some sellers count two test-pulse outputs alongside the two safety outputs and one auxiliary output. Only two of these are the functional safety outputs.
5. Can it monitor a two-channel emergency stop or safety gate?
Yes, when wired according to Pilz instructions. Input short detection and reset mode depend on the selected circuit. A qualified engineer must validate the complete safety function.
6. What does phase-out mean for ordering this part?
Pilz labels 774130 as a phase-out article. Confirm the required exact part number and current seller offer; do not assume an alternative article is a direct replacement.
7. Can I purchase when Indus MegaMart shows zero stock?
Yes. Its ordering policy allows orders and payment with zero available stock, with a stated delivery window of 7–14 days for quantities exceeding available stock.
8. Does the generated invoice include a GST number?
Indus MegaMart states its generated purchase invoices include its company GST number. Check the live product price and GST treatment on the exact order page.
Buy the exact Pilz PNOZ e1p 774130
Check the 24 V DC supply, semiconductor-output requirement, screw-terminal version, phase-out status and destination PIN code. Then continue to the exact Pilz 774130 listing to review current commercial terms and place your order.
Buy now – Pilz PNOZ e1p 774130.