Pilz PNOZ 1 Safety Relay 24 V AC, 3 NO / 1 NC (775600) in Bhopal
For replacement and machine-panel procurement in Bhopal, choose Pilz PNOZ 1 part 775600 when the approved design specifies a 24 V AC standalone safety relay with three normally-open safety contacts and one normally-closed auxiliary contact. The 90 mm-wide relay uses fixed screw terminals and monitors emergency-stop pushbuttons and safety gates. Check the exact model, current price, GST basis, selling quantity and delivery for your Bhopal pincode on the product listing before ordering.
View price and order Pilz 775600
Specifications for the 24 V AC PNOZ 1
|
Specification |
Details |
|
Manufacturer/model |
Pilz / PNOZ 1 / 775600 |
|
Supply |
24 V AC, 50–60 Hz; tolerance −15%/+10%; 5.5 VA |
|
Outputs |
3 NO instantaneous safety contacts; 1 NC auxiliary; 0 semiconductor outputs |
|
Input/starting |
1 or 2 channels without cross-short detection; automatic or manual start; feedback loop |
|
Safety contact ratings |
AC-1: 8 A at 240 V, 5 A at 400 V; DC-1: 8 A at 24 V; AC-15: 5 A at 230 V; DC-13: 7 A at 24 V (6 cycles/min). AC-1/DC-1 minimum 10 mA. |
|
Mounting/connection |
35 mm DIN rail; fixed screw terminals; flexible single-core conductor 0.2–4 mm² |
|
Dimensions/weight |
87 mm H × 90 mm W × 121 mm D; 500 g net |
|
Environment |
−10 to +55 °C; no condensation; housing IP40, terminals IP20; cabinet at least IP54 |
|
Diagnostics |
POWER, CH.1 and CH.2 LEDs |
|
Contact material |
Silver tin oxide with 0.2 µm gold coating |
|
OEM approvals/identification |
CE, UKCA, CCC, cULus Listed, TÜV, EAC; GTIN 4046548010190; OEM packaging unit 1 |
Select the relay for the existing safety circuit
For an emergency-stop circuit or guarded machine access, first confirm the supply and the required input diagnostics. This model supports single- or dual-channel configurations without detection of shorts across contacts; a dual-channel input does not by itself establish that a design meets its required performance level. The feedback loop can monitor suitable external contactors. Automatic start requires measures against unintended restart; manual start is not automatically equivalent to monitored reset. Have a qualified safety engineer assess and validate the complete circuit and any changes.
Match the physical mounting and load category when replacing a relay in a press, conveyor or other machine control panel where the approved design already specifies this model. Normal automatic or manual start takes 190 ms typically and up to 270 ms; the specified channel simultaneity limit is 140 ms. The E-stop response can be longer immediately after startup, so do not select the device from a typical response figure alone. Refer to the Pilz operating manual for contact protection, loading, connection and safety characteristics.
The PNOZ 1 family includes 775695 (24 V DC), 775620 (48 V AC), 775630 (110–120 V AC) and 775650 (230–240 V AC). These are different order numbers, not interchangeable supply variants.
Explore other Pilz safety relay options
Browse safety relays by application and specification
Ordering and delivery for Bhopal buyers
Choose the required quantity after checking the listed sale unit and GST treatment. Indus MegaMart accepts orders and payments even when available stock is insufficient. Under its ordering policy, quantities within available stock are delivered within 7 days; quantities exceeding available stock, including zero stock, are delivered within 7–14 days. Confirm serviceability for your delivery pincode before ordering. Purchase invoices contain the company GST number. For bulk or maintenance procurement, confirm the required quantity, product condition, warranty and return terms before purchase.
Frequently asked questions
1. Can I use 775600 on a 24 V DC supply?
No. The supply for 775600 is 24 V AC. Pilz 775695 is the 24 V DC version; check the entire safety design before replacing one with the other.
2. Can the NC contact be used as a fourth safety output?
No. The NC auxiliary contact is for signalling, such as a status indication. Use the three NO safety contacts for the designed safety circuit.
3. Does PNOZ 1 detect shorts between the two input channels?
No cross-short detection is provided. If the risk assessment requires that diagnostic capability, select an appropriately specified relay instead.
4. Is an 8 A contact rating valid for every connected load?
No. The permitted current depends on load category, voltage and switching conditions. For example, AC-15 is rated 5 A at 230 V; check the manual for protection and loading limits.
5. What is the emergency-stop response time?
The typical relay de-energisation time on an E-stop demand is 15 ms. Maximum is 30 ms when the preceding operating period is at least 6 seconds, but up to 400 ms for a shorter period. Power-loss de-energisation can also take up to 400 ms. Include the complete machine stopping time in the validated safety design.
6. How many relays are included in a purchase?
Pilz states one relay per manufacturer packaging unit. Check the actual selling quantity, pack and price basis on the product listing before placing an order.
7. Can I use the same relay to replace a different PNOZ 1 voltage variant?
Not on model name or housing size alone. Compare the order number, supply type and voltage, input diagnostics, reset arrangement, contact ratings and safety validation requirements.