Pilz S3UM 837260 Three-Phase Voltage Monitoring Relay in Nashik
For industrial buyers in Nashik looking for the exact Pilz S3UM 837260, this compact monitoring relay supervises overvoltage, undervoltage and phase sequence in three-phase AC systems. It uses a separate 24 V DC operating supply and is specified for a 230 V AC measuring voltage, so these two electrical values must not be confused. The device provides a changeover relay contact for signalling an out-of-range condition to a suitably engineered control circuit. Review the current product price and GST on Indus MegaMart, check the required order quantity and Nashik delivery pincode, and proceed to the exact 837260 listing to buy online.
Buy Pilz S3UM 837260 for Nashik Delivery
Select manufacturer part number 837260 (S3UM 24VDC UM 230VAC), confirm the current listed price and GST, and enter the destination pincode to check delivery details. Choose the required quantity before continuing to the exact product listing. For a repeat order, match the number on the existing relay label and the electrical drawing—not just the S3UM family name.
Order the exact Pilz S3UM 837260: View price and buy on Indus MegaMart
Verified Technical Specifications
|
Specification |
Detail |
|
Manufacturer/model/article |
Pilz / S3UM / 837260 |
|
Product family |
PMDsrange three-phase voltage monitoring relay |
|
Operating supply (Uᴮ) |
24 V DC; separate from measuring input |
|
Nominal monitored voltage (Uᴹ) |
230 V AC in a three-phase supply |
|
Monitoring functions |
Overvoltage, undervoltage, phase sequence; phase failure and asymmetry detection |
|
Measuring frequency range |
40–400 Hz |
|
Adjustable undervoltage threshold |
75–100% of rated monitored voltage |
|
Adjustable overvoltage threshold |
100–120% of rated monitored voltage |
|
Hysteresis/delay |
Approximately 2% hysteresis; selectable 0.5–10 s delay-on energisation |
|
Relay contacts |
1 auxiliary changeover contact (C/O) |
|
DC power consumption |
1.5 W |
|
Terminal construction |
Fixed screw terminals |
|
Dimensions (H × W × D) |
87 × 22.5 × 122 mm |
|
Operating ambient temperature |
−15 °C to +55 °C |
|
Housing / terminal protection |
IP40 housing / IP20 terminals; suitable protective panel enclosure required |
What the S3UM 837260 Monitors
The S3UM checks the condition of a three-phase voltage supply rather than measuring motor load current. It can detect when voltage moves above or below configured limits, and it evaluates phase order, phase loss and asymmetry. The 230 V AC measuring variant is intended for circuits that match this measuring specification; another S3UM article with a different Uᴹ rating is not automatically interchangeable.
Adjustable response for electrical supervision
For this standard 837260 variant, the undervoltage threshold may be adjusted across 75–100% of nominal measuring voltage and the overvoltage threshold across 100–120%. A selectable 0.5–10 s delay helps coordinate signalling with the control design. Qualified personnel should select settings according to the actual network, connected loads and protection scheme.
Relay output and control-circuit connection
One changeover auxiliary contact can convey the monitoring state to a PLC input, indication device or contactor-control circuit when correctly rated and wired. It is not a substitute for a dedicated machinery safety relay or a complete safety-rated stop function. Verify the contact duty and wiring arrangement against the Pilz instructions before installation.
Where This Monitoring Relay Fits
Typical selection contexts include control panels supervising three-phase equipment, electrical distribution monitoring in machinery, pump or fan control schemes, and conveyor or manufacturing lines that need a signal when the monitored network moves outside permitted conditions. These are application examples, not claims that the relay itself provides dry-run detection, motor overcurrent protection or a certified machine safety function.
Important Checks Before Ordering
- Check both voltages: 24 V DC is the relay operating supply; 230 V AC is its specified measuring voltage for the three-phase network.
- Confirm the actual three-phase system configuration, nominal voltage, frequency and phase-sequence requirements with the electrical design.
- Match part number 837260 against 837270/837271 and other S3UM versions, which have different measuring ratings or variants.
- Allow for the 22.5 mm-wide module and its 87 × 122 mm height/depth in the panel layout, with appropriate enclosure protection.
- Confirm the changeover contact rating, wiring, trip thresholds and delay with a qualified controls engineer.
- Review the sale unit, quantity, GST treatment, delivery-pincode result and applicable purchase terms on the exact product page before payment.
Ordering and Delivery Information for Nashik
Indus MegaMart accepts orders and payment even when the required quantity is greater than available stock, including zero-stock orders. Under its ordering policy, quantities covered by available stock are delivered within 7 days; quantities exceeding stock, including orders placed at zero stock, are delivered within 7–14 days. Enter your Nashik receiving pincode to check destination-specific delivery details and review the latest price and tax information before checkout.
For business procurement, confirm the selected quantity and product identity before placing the order. Purchase invoices include Indus MegaMart’s GST number; check the current item-level GST breakdown on the product listing.
Frequently Asked Questions
1. What is the difference between 24 V DC and 230 V AC on Pilz 837260?
The 24 V DC value is the operating supply for the S3UM 837260. The 230 V AC value is the nominal measuring voltage of the three-phase network that it monitors. They describe different electrical connections.
2. Does the Pilz S3UM 837260 monitor phase sequence and undervoltage?
Yes. Pilz identifies overvoltage, undervoltage and three-phase sequence monitoring, with detection of phase failure and asymmetry as part of the S3UM function.
3. What relay output does article 837260 provide?
It provides one auxiliary changeover relay contact (1 C/O) for monitoring-state signalling, subject to the manufacturer’s contact ratings and wiring instructions.
4. Can I replace 837260 with S3UM 837271?
Not without verifying the design. Article 837260 is the 230 V AC measuring version; 837271 is a 400/440 V AC measuring variant with different threshold characteristics. Matching the 24 V DC operating supply alone is insufficient.
5. Can this device replace a Pilz PNOZ safety relay?
No direct equivalence should be assumed. The S3UM monitors three-phase electrical conditions, while PNOZ safety relays are intended for defined safety-circuit functions. Use the appropriate device under the machine’s approved design.
6. Can I order when Indus MegaMart shows no stock?
Yes. Orders and payments remain accepted under Indus MegaMart’s policy. If stock is zero or the ordered quantity exceeds stock, the stated delivery timeline is within 7–14 days, subject to confirming destination delivery details.
7. How do I buy the correct S3UM for Nashik?
Open the Indus MegaMart listing for part number 837260, review the current price and GST, enter your Nashik delivery pincode, choose the quantity and proceed through the exact-product purchase page.
Order Pilz S3UM 837260 Monitoring Relay
Ready to purchase the Pilz S3UM 24 V DC / 230 V AC monitoring relay for a Nashik delivery address? Confirm article number 837260, check the live price, GST and pincode details, select your quantity and continue to the exact Indus MegaMart product page.
Buy Pilz S3UM 837260: Open exact product and continue to checkout