Buy Pilz PNOZ 8 Safety Relay 24 V DC, 3NO 1NC 2SO (774760) in Mandi
For a replacement safety relay in a Mandi machine-control panel, match the complete part number 774760 rather than ordering by the PNOZ 8 name alone. This standalone Pilz model uses a 24 V DC supply, three instantaneous normally-open safety contacts, one normally-closed auxiliary contact and two semiconductor signals. It monitors emergency-stop pushbuttons and safety-gate switches in correctly designed safety circuits. Its fixed screw terminals and 90 mm housing are especially relevant when checking an existing panel layout.
View price and order Pilz 774760
Ordering the PNOZ 8 for Mandi delivery
Review the current price, GST basis, selling unit and required quantity on the exact product listing before payment. Pilz lists one relay per packaging unit; confirm the seller’s applicable selling unit and included items separately. Check serviceability for your Mandi delivery pincode. Indus MegaMart accepts orders and payment even when available stock is zero. Under its delivery policy, quantities within available stock are delivered within 7 days; quantities exceeding available stock, including zero stock, are delivered within 7–14 days. Purchase invoices carry the company’s GST number.
Technical specifications
|
Parameter |
Specification |
|
Brand / model / MPN |
Pilz / PNOZ 8 / 774760 |
|
GTIN |
4046548061666 |
|
Supply and consumption |
24 V DC, −15%/+10%; 4.5 W |
|
Inputs and start modes |
2 inputs; single or dual channel; automatic, manual or monitored start |
|
Safety outputs |
3 instantaneous NO relay contacts |
|
Auxiliary contact |
1 instantaneous NC, signalling only |
|
Semiconductor outputs |
2 signals, 24 V DC / 50 mA, DC-12; short-circuit protected |
|
Contact ratings |
AC-1: 8 A at 240 V AC; DC-1: 8 A at 24 V DC; AC-15: 5 A at 230 V AC; DC-13: 7 A at 24 V DC (6 cycles/min) |
|
Thermal current, AC-1/DC-1 |
8 A per contact with one or two loaded contacts; 7 A with three |
|
E-stop release / power failure |
15 ms typical, 30 ms max / 100 ms typical, 200 ms max |
|
Mounting / terminals |
35 mm DIN rail; fixed screw terminals |
|
Dimensions (H × W × D) / mass |
87 × 90 × 121 mm / 450 g |
|
Environment |
−10 to +55 °C, no condensation; housing IP40, terminals IP20, cabinet at least IP54 |
|
OEM safety characteristics |
PL e / Category 4 / SIL 3, subject to complete safety-function validation |
|
OEM approvals listed |
CCC, CE, EAC, TÜV, UKCA, cULus Listed |
Separate safety switching from fault diagnostics
The three NO contacts form the safety switching paths. The NC auxiliary contact can indicate relay state. Y32 reports contact state; Y35 reports a fault. These two semiconductor outputs help a separate monitoring system distinguish safety-contact status from an internal-fuse fault. LEDs indicate power, channel state and fault status. Do not use the NC contact or either semiconductor signal as a safety output. Select the load using its utilisation category and the combined contact loading, rather than assuming that 8 A applies to every circuit.
Selection for emergency stops and safety gates
PNOZ 8 supports single-channel or dual-channel input wiring, including dual-channel configurations with or without cross-short detection. The input, start and feedback circuits are rated at 24 V DC. The feedback path can be used to monitor external switching devices as specified in the manufacturer’s manual. Choose automatic, manual or monitored start according to the validated machine safety design; resetting an emergency stop must not create an unsafe restart. Do not substitute a PNOZ 8 AC-supply variant for 774760. Confirm panel clearance, fixed terminal configuration, contact protection and the actual switching duty. Use the exact Pilz operating manual and qualified personnel for installation and testing.
For alternative configurations, explore Pilz products and compare safety relays in the electrical and industrial automation range.
Frequently asked questions
1. What does 3NO 1NC 2SO mean on 774760?
It denotes three normally-open safety contacts, one normally-closed auxiliary contact and two semiconductor signalling outputs. The latter three outputs are not additional safety switching contacts.
2. Can the PNOZ 8 774760 be powered by 24 V AC?
No. This order number is the 24 V DC version. Check the supply type as well as voltage before replacing an installed relay.
3. Can both semiconductor outputs drive a safety contactor?
They are intended for status and fault signalling, not safety-related load switching. Their rating is 24 V DC, 50 mA (DC-12); check the receiving input and the external supply requirements in the manual.
4. Is the 30 ms response the total machine stopping time?
No. It is the manufacturer’s maximum relay release time on an emergency-stop demand. Power failure has a different release time, and the machine’s actual stopping time also depends on its other safety components and mechanics.
5. Does this module guarantee Category 4 or SIL 3 for my machine?
No. Pilz lists PL e, Category 4 and SIL 3 characteristic data for the device. The complete safety function must be designed and validated for the required performance level or SIL.
6. What should I confirm for an institutional order?
Use MPN 774760 and GTIN 4046548061666 on the purchase request. Confirm the listed selling unit, quantity, product condition, warranty and return terms before payment.
7. Can I order this relay when the listing shows zero stock?
Yes. Indus MegaMart accepts orders and payments even at zero stock. Delivery for quantities exceeding available stock follows the 7–14 day policy, with destination serviceability to be confirmed.
Buy Pilz PNOZ 8 774760 — view the exact product and order for Mandi