Buy Pilz S1WP 9A True Power Monitoring Relay 110-230VAC/DC (890070) in Faridabad
Order the Pilz S1WP 890070 from Indus MegaMart when your Faridabad plant or panel project requires active-power monitoring on a single-phase or three-phase electrical machine. This 9 A PMDsrange model has a 110–230 V AC/DC supply designation, a selectable analogue signal and an auxiliary changeover relay contact for load-limit indication. It is designed for true-power monitoring, including frequency-controlled motor applications.
Check the current price, GST basis, selling unit and required quantity on the exact product listing. Confirm delivery for your Faridabad pincode before placing the order.
View price and buy Pilz S1WP 890070
Technical specifications of Pilz 890070
|
Parameter |
Specification |
|
Brand / MPN / GTIN |
Pilz / 890070 / 4046548007039 |
|
Product family |
PMDsrange S1WP true-power monitor |
|
Supply UB |
110–230 V AC/DC product designation; 5 VA at 230 V AC; AC supply frequency 30–400 Hz |
|
Measurement UM |
0–550 V three-phase; 0–320 V single-phase AC/DC |
|
Measuring current IM |
9 A variant; external CT required for sustained AC motor current above 9 A |
|
Measurement frequency |
0–1000 Hz |
|
Selectable power full scale |
0.95, 1.9, 2.85, 3.8, 4.76, 5.7, 6.7, 7.6, 8.6 kW; ranges 1–4 not for DC |
|
Monitoring mode |
Selectable upper-limit overload or lower-limit underload; 5–100% of selected range; hysteresis 15% of threshold |
|
Timing |
Relay response 0.1–20 s; startup suppression 0.1–30 s; analogue response 60 ms |
|
Digital indication |
One auxiliary changeover contact 11/12/14; power and fault LEDs |
|
Analogue output |
Selectable 0–10 V DC (load ≥1 kΩ) or 4–20 mA (≤0.5 kΩ) in motor operation; generator voltage 0 to −10 V (≥2 kΩ) |
|
Contact ratings |
AC-1: 0.1–5 A at 240 V; DC-1: 0.1–5 A at 24 V; AC-15: 0.1–1.8 A at 230 V; DC-13: 0.1–1.5 A at 24 V |
|
Mounting / terminal |
DIN rail; fixed screws; 0.6 Nm max; single flexible conductor 0.20–4 mm² |
|
Dimensions / mass |
87 × 22.5 × 121 mm (H×W×D); 140 g net, 150 g gross (exact catalogue) |
|
Environment |
0 to +55 °C; storage −40 to +85 °C; no condensation; IP40 housing, IP20 terminals, IP54 min cabinet |
|
Approvals / pack |
CE, CCC, UKCA, cULus Listed; OEM packaging quantity 1, not seller sale-unit confirmation |
Use active power to identify changes in machine load
A current reading alone does not always reflect a motor’s useful electrical load. The S1WP evaluates true (active) power using voltage, current and power factor. In upper-limit (UL) mode it signals excessive power; in lower-limit (LL) mode it signals power below the selected threshold. The power and fault LEDs help distinguish supply status from a load-limit event.
For example, a conveyor drive with a sustained rise in load may need an overload indication, whereas a pump with an abnormal drop in power may need an underload indication. These are selection examples, not guaranteed fault diagnoses: establish the normal load profile and confirm the threshold for the particular equipment. The adjustable startup suppression and relay response time help avoid nuisance indications during acceleration or brief fluctuations.
Select the measurement range and output before ordering
Separate supply voltage (UB) from measurement voltage (UM). For this variant, the maximum measuring voltage is 550 V for the three-phase arrangement and 320 V for single-phase AC/DC. The nine selectable full-scale values run from 0.95 to 8.6 kW under the documented range conditions; settings 1–4 are not suitable for DC. A full-scale value is not a motor nameplate rating. Set the threshold within 5–100% of the chosen range and account for the fixed 15% threshold hysteresis. Sustained AC motor current above 9 A requires a correctly selected external current transformer and revised scaling.
The single changeover output is an auxiliary contact for indication or suitably rated contactor control, not a 9 A motor switch. Choose 0–10 V or 4–20 mA to suit the receiving input. Use the specified contact utilisation category, impedance and protective devices. Installation and commissioning belong to qualified electrical personnel following the Pilz instructions; the monitor is not a drop-in replacement for an emergency-stop or guard-monitoring relay.
Compare S1WP order numbers before replacing an installed unit
|
MPN |
Selection difference |
|
890070 |
9 A; 110–230 V AC/DC supply; UM 0–550 V three-phase; adjustable startup suppression. |
|
890071 |
Same headline voltage/current configuration, but Ts=0 startup suppression variant. |
|
890030 |
9 A; 24 V DC supply; UM 0–550 V three-phase. |
|
890060 |
9 A; 110–230 V AC/DC supply; UM 0–415 V three-phase. |
|
890170 |
18 A; 110–230 V AC/DC supply; UM 0–550 V three-phase. |
For panel refurbishment, match the full part number, supply, measurement range, output scaling and time behaviour. Similar housings and series names do not establish interchangeability. Compare the related versions if the original specification differs.
Compare Pilz 890071 (Ts=0)
Compare Pilz 890030 (24 V DC supply)
Compare Pilz 890170 (18 A)
Purchasing for Faridabad industrial sites
For maintenance spares or a multi-unit panel bill of materials, specify 890070 and the actual number of relays required. Pilz lists one unit per manufacturer packaging unit; confirm the Indus MegaMart selling unit, quantity and total GST basis before payment. Check whether any external current transformer is required separately. Confirm applicable warranty and returns terms for your procurement approval rather than assuming they are included.
Indus MegaMart serves Faridabad NCR industrial procurement. For serviceable destinations, its standard order policy specifies delivery within 7 days when the requested quantity is within available stock and 7–14 days when the requested quantity exceeds stock, including zero stock. Orders and payment remain accepted when stock is insufficient. Check the destination pincode and quantity for your order. Purchase invoices contain the company’s GST number.
Browse safety controllers and modules
Explore Pilz products
Explore electrical and industrial automation
Frequently asked questions
1. Can the 890070 measure 550 V on a single-phase circuit?
No. The 550 V upper measuring range applies to the three-phase configuration. For single-phase AC/DC the corresponding limit is 320 V. Match the measurement circuit, not just the voltage printed in the product name.
2. Does the 9 A rating refer to the output contact?
No. It identifies the measuring-current version. The auxiliary relay contact has separate ratings; for example AC-15 is rated up to 1.8 A at 230 V.
3. Can I monitor a motor drawing more than 9 A?
For sustained AC motor current above 9 A, use a suitable external current transformer as specified in the Pilz manual. Confirm the transformer ratio and recalibrate the power range; do not assume direct connection is suitable.
4. Can I connect this relay to an analogue PLC input?
Yes, if the input and scaling suit the selected signal, either 0–10 V DC or 4–20 mA in motor operation. Check the input impedance and reference arrangement. The voltage option can also represent generator operation down to −10 V.
5. Is the 890071 a direct equivalent?
It shares the 9 A and voltage-range designation but is identified separately by Pilz as the Ts=0 version. Confirm start-up suppression requirements and the original part number before substituting it.
6. Can this device replace an emergency-stop safety relay?
Do not choose it for that purpose based on its catalogue category. S1WP measures active power and changes an auxiliary contact at a configured limit. A protective safety function requires a suitable, validated safety architecture.
7. How do I order the correct unit and get a GST invoice?
Use MPN 890070 on the order. Pilz specifies one unit per manufacturer package; confirm the merchant selling unit and GST-inclusive or exclusive price on the product page before payment. Indus MegaMart purchase invoices carry the company GST number.
Order Pilz S1WP 890070 for Faridabad delivery
Confirm the 9 A model and supply/measuring voltage, choose your required quantity and review the product price and delivery details before purchasing.
Buy Pilz S1WP 9A monitoring relay – 890070