Pilz 774729 PNOZ X6 Safety Relay 24V AC/DC, 3NO in Faridabad
Order the Pilz PNOZ X6 safety relay, article 774729, for your Faridabad machine control panel or maintenance requirement. This standalone electromechanical relay accepts 24 V AC or DC and provides three instantaneous normally open safety contacts for emergency-stop and safety-gate monitoring. Its fixed screw terminals and 45 mm housing width are important when matching an existing panel. Check the current price, GST basis, selling unit and required quantity on the exact Indus MegaMart listing before ordering.
Buy Pilz PNOZ X6 774729 — check price and availability
Technical specifications of the 774729
|
Parameter |
Specification |
|
Manufacturer/model |
Pilz PNOZ X6; MPN 774729 |
|
Supply |
24 V AC or DC; −15%/+10%; AC 50–60 Hz; 3 VA AC / 2 W DC |
|
Safety outputs |
3 instantaneous NO; 13–14, 23–24, 33–34; no semiconductor output |
|
Inputs and start |
1 or 2 channels; no detection of shorts across contacts; automatic, manual or monitored start |
|
AC1 / DC1 |
8 A at 240 V AC / 8 A at 24 V DC (load and thermal limits apply) |
|
AC15 / DC13 |
5 A at 230 V AC / 7 A at 24 V DC (DC13: 6 cycles/min) |
|
Thermal current per contact |
With AC supply: 8 A / 7.3 A / 6 A for 1 / 2 / 3 loaded contacts; with DC supply: 8 A for 1–3 contacts (AC1/DC1) |
|
Response / recovery |
E-stop de-energisation: 15 ms typical, 30 ms maximum; supply failure: 110 ms typical, 160 ms maximum |
|
Mounting / terminals |
35 mm DIN rail; fixed screw terminals; IP54 minimum cabinet |
|
Physical size / mass |
87 × 45 × 121 mm (H × W × D); 295 g net |
|
Environment |
−10 to +55 °C operation; IP40 housing, IP20 terminals; no condensation |
|
Safety characteristic data |
PL e, Cat. 4, SIL 3 at component level; complete safety function must be assessed |
|
GTIN / packaging |
4046548010435; OEM packaging unit: 1 relay |
The ratings above describe the relay, not the stopping time or safety performance of an entire machine. Consult the operating manual for the actual load, contact protection and safety calculations.
Pilz operating manual — PNOZ X6
Select it for the safety function, not just the contact count
For a conveyor emergency-stop circuit or a guarded packaging station, the three safety contacts can form part of a validated shutdown circuit. When the input circuit opens, the safety contacts open redundantly. A panel builder can use the three output paths within the approved design; the relay itself is not a substitute for correctly selected contactors, guards or a complete safety assessment.
The X6 supports single-channel or dual-channel input wiring, but it has no detection of shorts across contacts in its dual-channel input configuration. The start/feedback circuit does not detect short circuits or shorts across contacts either. Ensure suitable fault-exclusion measures and validate the selected start mode; automatic restart is not suitable wherever unexpected restart presents a hazard. Installation and commissioning require qualified personnel and the manufacturer’s instructions, including a SELV/PELV supply and suitable protective enclosure.
When to choose another relay
If the required circuit depends on cross-contact short detection, a dedicated two-hand safety function, timed outputs or a separate signalling contact, assess another model rather than treating the X6 as an interchangeable solution. This is a 3NO instantaneous relay, not a two-hand control relay or a programmable safety controller.
774729 versus the 774726 PNOZ X6
The 774729 uses 24 V AC/DC. The 774726 is a different PNOZ X6 article with a 230–240 V AC supply; Pilz lists that mains-voltage variant as discontinued. The shared X6 designation and three normally open contacts do not make the two supply versions interchangeable. For a retrofit, check the nameplate, supply, terminals, load ratings, reset/feedback design and required safety function before selecting any replacement.
Buying for Faridabad maintenance and panel projects
For a planned replacement, keep the full article number on the purchase order and specify the quantity needed for the panel and any maintenance spares. Enter the receiving Faridabad pincode when checking delivery on the product listing. Indus MegaMart purchase invoices contain the company’s GST number; verify the billing details, item condition, warranty and return terms before ordering. For a larger project, confirm the quantity and total payable amount rather than assuming a single-relay OEM pack determines the seller’s order unit.
If you are selecting another configuration, compare the available models by voltage, contact type and safety function first.
Explore safety relays
Browse Pilz products
Electrical & industrial automation components
Frequently asked questions
1. Does 774729 accept both 24 V AC and 24 V DC?
Yes. The PNOZ X6 article 774729 is rated for either 24 V AC or 24 V DC. The manual specifies a supply tolerance of −15%/+10%; AC operation is 50–60 Hz.
2. Does PNOZ X6 detect cross-shorts between input contacts?
No. Its dual-channel mode does not detect shorts across the input contacts. The start/feedback loop also lacks short-circuit and cross-contact-short detection. The safety design must address these faults appropriately.
3. Can I use the 774729 for two-hand press control?
Do not select this article as a two-hand control relay. Pilz specifies emergency-stop pushbuttons and safety gates as its intended applications. Use a device and circuit expressly approved for the required two-hand safety function.
4. Does PL e automatically certify my machine?
No. Pilz lists PL e, Category 4 and SIL 3 for the component, subject to the manual’s conditions and relay contact life. The achieved level of the complete safety function depends on all components, wiring and risk assessment. Single-channel input use may lower the achieved level.
5. Are the three outputs rated at 8 A in every application?
No. The 8 A figures relate to AC1 at 240 V and DC1 at 24 V. AC15 and DC13 control loads have different limits; simultaneous contact loading can reduce the permitted current, particularly with an AC supply.
6. How many relays are in the manufacturer pack?
Pilz specifies one relay per packaging unit. The optional COVER P-93 (774090) is a separate accessory, not an assumed inclusion. Confirm the Indus MegaMart selling unit and quantity before placing your order.
7. What approvals are listed by Pilz?
The manufacturer lists CCC, CE, EAC, TÜV, UKCA and cULus Listed for this article. Check the relevant documentation and project-specific compliance requirements before installation.
8. Can I order more than the available stock for Faridabad?
Yes. Indus MegaMart accepts orders and payment even when stock is insufficient or zero. Its standard policy is delivery within 7 days for quantities within available stock and 7–14 days for higher quantities or zero stock. Check the delivery estimate for your Faridabad pincode and required quantity before paying.
Buy Pilz 774729 PNOZ X6 24V AC/DC 3NO — view current price and order