Buy Pilz PNOZ XV2P Safety Relay 30/24VDC (777500) in Dhanbad
Order the Pilz PNOZ XV2P safety relay, article 777500, for your Dhanbad control panel or maintenance requirement. This standalone 24 V DC relay combines two instantaneous and two delayed normally open safety contacts, with a 30-second maximum selectable off-delay. It suits engineered emergency-stop and safety-gate circuits that need distinct immediate and delayed switching stages. Match the exact part number, screw-terminal connection and approved timing before purchasing. Check the current product price, tax details and required order quantity on the product listing.
Buy Pilz PNOZ XV2P 777500 — check price and order
Technical specifications of Pilz 777500
|
Parameter |
Exact specification |
|
Article / series |
777500 / PNOZ XV2P, PNOZ X |
|
Supply / consumption |
24 V DC (−15%/+10%); 4.5 W |
|
Safety outputs |
2 instantaneous NO + 2 off-delay NO; no semiconductor outputs |
|
Selectable off-delay |
0.1, 0.5, 1, 2, 4, 6, 8, 10, 15, 20, 25, 30 s |
|
Time accuracy |
−15% / +15% +50 ms; repeatability 2% |
|
Input / start |
Two inputs; 1- or 2-channel; cross-short detection option; automatic or monitored start |
|
Output load maxima |
AC-1 8 A at 240 V; DC-1 8 A at 24 V; AC-15 5 A at 230 V; DC-13 7 A at 24 V (6 cycles/min) |
|
Housing / environment |
94 × 45 × 121 mm (H × W × D); 360 g; −10 to +55 °C; no condensation |
|
Protection / terminals |
IP40 housing, IP20 terminals, IP54 mounting enclosure; plug-in screw terminals |
|
Approvals |
CCC, CE, UKCA, cULus Listed, EAC, TÜV (OEM listing) |
|
GTIN |
4046548009637 |
Check load and timing before selection
The 8 A AC-1/DC-1 maximum is not a blanket rating for all four loaded contacts. Under the manual’s conventional thermal-current conditions, the per-contact limit decreases to 7 A with two contacts loaded, 5.7 A with three, and 5 A when four are loaded. Apply the applicable utilisation category, simultaneous-loading limits, protective devices and service-life conditions. The nominal delay has a tolerance; it is not a precise measurement of actual machine stopping time.
Applications and safety-performance limits
In a packaging-machine or conveyor control panel, the relay can be considered where a validated emergency-stop or guard-switch circuit calls for different output switching times. The direct contacts can initiate the designed immediate action, while delayed contacts support a subsequent interruption. The relay does not itself measure a motor’s speed or provide a drive braking function. A qualified safety engineer must determine the stop sequence, input configuration, reset method and external devices from the machine risk assessment. Single-channel input wiring does not provide the same redundancy as dual-channel wiring.
| Output type |
OEM component safety data |
|
Instantaneous |
PL e / Category 4 / SIL 3 |
|
Delayed, setting below 30 s |
PL d / Category 3 / SIL 3 |
|
Delayed, setting 30 s or above |
PL c / Category 1 / SIL 1 |
These are component characteristic values, not a certification of the completed safety circuit. The 30 s setting is especially important when the required performance level is higher than PL c for the delayed function. Follow the Pilz operating manual and validate the complete machine before returning it to service.
Select the right XV2P variant
|
Pilz article |
Off-delay |
Terminals |
|
777500 (this product) |
0.1–30 s, selectable |
Plug-in screw |
|
777502 |
Up to 3 s, selectable |
Plug-in screw |
|
777503 |
1 s fixed |
Plug-in screw |
|
777504 |
0.5 s fixed |
Plug-in screw |
|
787500 |
Up to 30 s, selectable |
Plug-in spring-loaded |
If the relay is being purchased against an existing bill of materials, use the exact article number rather than the family name alone. The timing range and terminal arrangement affect selection. For alternative requirements, explore the related ranges below.
Browse Pilz automation products
Compare safety relays
Price, ordering and delivery in Dhanbad
Pilz specifies one device per manufacturer packaging unit for 777500. Before finalising your order, confirm the selling unit and applicable minimum quantity on the Indus MegaMart listing, particularly when ordering multiple relays for maintenance spares or panel production. Review the current price and GST breakup. Generated purchase invoices contain the company’s GST number. Check the warranty and return terms for your exact order before payment.
Enter your Dhanbad delivery pincode and required quantity when checking the product listing. Indus MegaMart’s ordering policy allows orders and payment even when available stock is zero. For a serviceable destination, the policy specifies delivery within 7 days if the order quantity is within available stock; delivery is within 7–14 days if the quantity exceeds available stock, including zero stock. Confirm the delivery details shown for your order before payment.
Frequently asked questions
1. Does 30/24VDC mean it accepts a 30 V DC power supply?
No. Article 777500 is rated for a 24 V DC supply. The 30 denotes the maximum selectable off-delay in seconds.
2. Are all four contacts instantaneous?
No. Two normally open safety contacts respond without the selected delay; the other two open after the selected off-delay. Use the contact type required by the validated safety function.
3. Does the 30-second selection retain the same safety rating as the shorter delay settings?
No. Pilz distinguishes delayed contacts below 30 s (PL d, Category 3, SIL 3) from delayed contacts at 30 s or above (PL c, Category 1, SIL 1). The instantaneous contact data is PL e, Category 4, SIL 3. The complete machine safety function requires separate validation.
4. Can I replace a 777502 or a 787500 with a 777500?
Do not assume interchangeability. The 777502 has a selectable delay limited to 3 s, while 787500 uses spring-loaded terminals. Confirm approved timing, terminal layout and the machine’s safety assessment before substituting.
5. Does the relay itself control braking or prove that a motor has stopped?
No. Its contact timing can form part of a validated stopping circuit, but it does not measure speed or standstill. Use appropriate external equipment for the required safety function.
6. Which spare terminal set is listed for this model?
Pilz lists article 374281 as the optional P3 + P4 screw-terminal spare set. Confirm whether additional spare terminals are needed separately from the relay.
7. How do I confirm the price and quantity for a Dhanbad purchase?
Open the exact product listing for 777500, check the current price and tax presentation, confirm the merchant selling unit, and select the required quantity. Use your delivery pincode to check fulfillment.
8. Can I place an order if the displayed stock is zero?
Yes. Indus MegaMart accepts orders and payment even at zero available stock. Under its ordering policy, quantities above available stock, including zero stock, have a 7–14 day delivery timeline. Confirm the delivery details for your pincode before purchase.
Buy Pilz PNOZ XV2P Safety Relay 30/24VDC (777500) — order online