Pilz S1IM 828035 Current Monitoring Relay 24 V DC in Belgaum
Buy the Pilz S1IM current monitoring relay, part number 828035, for an industrial control-panel requirement in Belgaum through Indus MegaMart. This 24 V DC PMDsrange unit monitors maximum electrical current using selectable measurement ranges and signals the configured condition through an auxiliary changeover contact. It has a narrow 22.5 mm housing and fixed screw terminals. Before ordering, confirm the exact S1IM UP version, the electrical measuring range, the current GST-inclusive offer, the seller-listed quantity and delivery serviceability for your Belgaum pincode.
Check Current Price and Buy Pilz 828035 in Belgaum
Check the exact 828035 product listing for the current price, GST breakdown, displayed stock and quantity options. Enter your delivery pincode to check whether the order can be served at your Belgaum address. Indus MegaMart accepts orders and payment even when the requested quantity exceeds stock, including zero-stock orders. Under its ordering policy, stock-covered orders are delivered within 7 days, while quantities above stock and zero-stock orders are delivered within 7–14 days, subject to pincode serviceability.
View Pilz S1IM 828035 price and place an order
Manufacturer Specifications for S1IM 828035
|
Specification |
Detail |
|
Brand / model / part number |
Pilz / S1IM 24VDC IM 0.01-15 A UP / 828035 |
|
Product class and function |
PMDsrange electronic current-monitoring relay; supervises maximum current values |
|
Rated operating supply |
24 V DC (not a 24 V AC supply variant) |
|
DC power consumption |
1 W |
|
Current selection |
12 selectable ranges; exact-product Pilz datasheet specifies 0.01–15 A |
|
Measuring input polarity |
UP version: measuring inputs are not polarity-sensitive |
|
Measurement frequency |
DC and 40–400 Hz AC measuring signals |
|
Auxiliary relay output |
1 changeover (C/O) auxiliary contact; not a dedicated E-stop safety output |
|
Operating modes |
Normally energized / normally de-energized; fault-latching / non-latching |
|
Connections |
Fixed screw terminals |
|
Housing dimensions (H × W × D) |
87 × 22.5 × 121 mm |
|
Temperature range |
−15 to +55 °C |
|
Housing protection |
IP40 housing; suitable protective cabinet selected for installation |
|
Manufacturer GTIN |
4046548007565 |
How the S1IM Current-Monitoring Function Works
The S1IM evaluates electrical current against a selected maximum-current threshold. When the monitored value reaches the configured condition, the relay can provide an indication for the surrounding control system. This can help a panel designer recognize an overcurrent-related operating condition, provided the measurement circuit, threshold, response characteristics and downstream logic have been engineered for the actual equipment.
Range, Timing and Operating Mode Matter
Pilz specifies twelve selectable current ranges for this UP variant, with non-polarity-sensitive measuring inputs. Its operating modes include normally energized or normally de-energized relay behavior and latching or non-latching fault options. Engineers should establish the expected current, permissible transient conditions, appropriate hysteresis and response timing from the Pilz instructions before setting the relay. Do not use the model name alone to infer the correct current threshold for a motor, pump or other load.
Suitable Applications and Selection Limits
The verified application is monitoring maximum current in a suitable single-phase measuring circuit. For example, a control-panel designer may use the relay to supervise a defined current threshold on compatible machinery or process equipment and make the status available to a control circuit. It does not directly replace a phase-monitoring relay, a voltage-monitoring relay or a purpose-built emergency-stop safety relay. Electrical protection devices, installation wiring, sensing range and equipment safety design must be specified separately.
Confirm the Exact 828035 Variant
Part 828035 is the S1IM UP version with a 24 V DC power supply, non-polarity-sensitive measuring inputs and fixed screw terminals. Other Pilz monitoring relays can have different supply voltages or monitor different electrical conditions. Match the complete part number, measurement specification, terminal arrangement and panel space before replacing an existing module.
Belgaum Procurement, Delivery and Related Pilz Products
For Belgaum procurement, use the national product listing to verify actual offer details and check the destination pincode before payment. For alternative monitoring functions, compare the required electrical parameter rather than selecting solely by the Pilz brand or 24 V supply. Browse the related Pilz selection and safety controllers and modules category if your project needs a different control or monitoring component.
Browse Pilz industrial automation components
View safety controllers and modules
Frequently Asked Questions
1. What does the Pilz S1IM 828035 monitor?
The S1IM 828035 monitors maximum electrical current in a configured measuring circuit. It is a current-monitoring relay, not an interchangeable replacement for a voltage, phase-sequence or emergency-stop safety relay.
2. Does Pilz S1IM 828035 require a 24 V DC supply?
Yes. The exact Pilz 828035 is a 24 V DC supply version. Check the supply separately from the AC/DC current that the measuring input is intended to supervise.
3. What current range does the 828035 support?
The exact-product Pilz datasheet identifies 12 selectable measuring ranges from 0.01 A to 15 A. Confirm the selected range and permissible loading against the current operating instructions before commissioning.
4. Can it measure current with reversed input polarity?
The UP designation denotes measuring inputs that are not polarity-sensitive. Follow Pilz wiring instructions and select the proper range for the monitored circuit.
5. How many output contacts are provided?
Pilz identifies one auxiliary changeover contact. Its function is to signal the monitored threshold condition; it must not be treated as a ready-made certified emergency-stop safety circuit.
6. How can I order 828035 for Belgaum if the listed stock is insufficient?
Indus MegaMart accepts orders and payment even when the ordered quantity exceeds listed stock or stock is zero. Under its ordering policy, stock-covered orders are delivered within 7 days, while above-stock or zero-stock orders are delivered within 7–14 days, subject to delivery-pincode serviceability.
7. Where can I confirm the current GST price and sales quantity?
Use the exact Pilz 828035 product listing on Indus MegaMart to review the current GST-inclusive price, displayed stock, seller-listed sale unit and available purchase options before checkout.
Order the Exact Pilz S1IM 828035
Confirm part number 828035, the measuring range, current GST-inclusive price and seller-listed quantity, then check your Belgaum pincode and complete the order through the exact Indus MegaMart product listing.
Buy Pilz S1IM 828035 on Indus MegaMart