Pilz 777538 PNOZ XV3.1P 24-240 V AC/DC Safety Relay in Ambattur
Buy the Pilz PNOZ XV3.1P safety relay, article 777538, from Indus MegaMart for industrial control-panel procurement in Ambattur. This wide-range 24–240 V AC/DC model combines three immediate normally open safety contacts with two normally open contacts that open after a selectable off-delay of 0.3 to 300 seconds. It is intended for safety circuits such as emergency-stop and guard monitoring where the machine design requires separate immediate and timed switching paths.
Check the exact model, current price, GST breakup, selling unit and required quantity on the product listing. Confirm delivery for your Ambattur pincode before ordering; use article 777538 on your bill of materials to avoid a shorter-delay or spring-terminal version.
Buy Pilz 777538 — check price and place your order
Technical specifications of Pilz 777538
|
Parameter |
Specification |
|
Brand/article |
Pilz PNOZ XV3.1P; 777538 |
|
Supply voltage |
24–240 V AC/DC; −15%/+10%; AC 50–60 Hz |
|
Safety output groups |
3 instantaneous NO (13–14, 23–24, 33–34); 2 off-delayed NO (57–58, 67–68) |
|
Auxiliary output |
1 instantaneous NC (41–42), not for safety circuits; no semiconductor output |
|
Selectable off-delay |
0.3, 5, 10, 20, 40, 60, 80, 100, 150, 200, 250, 300 s; discrete settings |
|
Timing |
−15% / +15% plus 50 ms; 2% repetition accuracy; E-stop immediate release 15 ms typical, 30 ms max |
|
Inputs/start |
Single or dual channel; dual channel with or without cross-short detection; automatic or monitored start; feedback loop |
|
Contact rating |
AC1: 8 A at 240 V AC; DC1: 8 A at 24 V DC; AC15: 5 A at 230 V AC; DC13: 7 A at 24 V DC (6 cycles/min) |
|
Thermal limits |
1/2/3/4/5 loaded contacts: 8/7.8/6.5/5.5/5 A per contact (AC1/DC1, AC or DC supply) |
|
Mounting and termination |
35 mm DIN rail; plug-in screw terminals; single flexible core 0.25–2.5 mm² |
|
Dimensions / mass |
94 × 90 × 121 mm (H × W × D); 540 g net |
|
Environment |
−10 to +55 °C; 93% RH at 40 °C, no condensation; IP40 housing, IP20 terminals, IP54 minimum cabinet |
|
OEM approvals |
CCC, CE, EAC, TÜV, UKCA, cULus Listed |
|
GTIN / OEM packaging |
4046548009453; 1 unit per manufacturer package |
How the two contact groups operate
When the monitored input circuit opens, the three instantaneous safety contacts open without the selected timing delay. The two delayed contacts open after the selected interval. The auxiliary NC contact changes state for signalling. This separation can support a validated stopping sequence, but the relay does not measure actual speed or confirm that hazardous motion has stopped.
The 300-second marking identifies the upper selectable off-delay, not a 300 V supply. A reset can terminate the timing cycle early. The selected delay is not a guarantee of how long a machine will take to stop; allow for timing tolerance, the response to supply failure, actuator behavior and the risk assessment.
Safety performance depends on the output and delay
|
Output / setting |
Component characteristic |
|
Instantaneous safety contacts |
PL e / Category 4 / SIL 3 |
|
Delayed safety contacts below 30 s |
PL d / Category 3 / SIL 3 |
|
Delayed safety contacts at or above 30 s |
PL c / Category 1 / SIL 1 |
These are manufacturer component-level values, not a rating for the installed machine. A longer delay may not meet the required performance level. Have a qualified person validate all parts of the safety function, safe stopping time and restart behavior.
Selecting the relay for a control panel or replacement
Supply, wiring and a safe restart
Use this article where the approved circuit calls for the wide-range supply and the exact two-group contact arrangement. A single-channel circuit is not redundant; cross-contact short detection depends on the selected dual-channel arrangement and must be validated. Automatic start can re-enable the relay when the safeguard is reset, so prevent unexpected machine restart through the approved circuit design. Monitored start and feedback are available according to the manufacturer’s wiring instructions.
Emergency-stop buttons and safety gates are typical selection contexts. For example, a panel builder may need immediate switching of one safety path and delayed isolation of another after a controlled stop. Do not treat the timing function by itself as safe speed monitoring or permission to unlock a guard. Confirm the exact interface for electronic sensors; the direct electronic light-guard example in the manual applies to designated 24 V DC-only variants, not this wide-range article.
Consult the Pilz PNOZ XV3.1P operating manual
Compare the correct delay variant
|
Pilz article |
Supply / delay / connection |
|
777538 |
24–240 V AC/DC; 0.3–300 s; plug-in screw |
|
777530 |
24–240 V AC/DC; 0.1–30 s; plug-in screw |
|
777532 |
24–240 V AC/DC; 0.1–3 s; plug-in screw |
|
787538 |
24–240 V AC/DC; up to 300 s; plug-in spring (OEM lists unavailable) |
A matching series name does not establish interchangeability. Match the required discrete delay, output allocation, safety level, cabinet clearance and connection type against the original nameplate and engineering drawings before changing an article number.
Ordering, packaging and delivery for Ambattur
Pilz lists one unit per manufacturer packaging unit; confirm the merchant selling unit, accessories and order quantity on the listing before payment. The optional replacement screw-terminal sets are 374281 (P3+P4) and 374282 (P5+P5). For maintenance stock or project purchases, specify the complete article number and required quantity; confirm item condition, warranty and return terms before committing to a shutdown purchase.
For a Ambattur panel shop or plant maintenance team, enter the destination pincode on the exact product page and confirm delivery against the required quantity. Indus MegaMart’s standard order policy is delivery within 7 days for quantity within available stock and 7–14 days when the quantity exceeds available stock, including zero stock. Order placement and payment are accepted even when stock is insufficient. Confirm the actual schedule with the merchant if the displayed delivery estimate differs. Purchase invoices contain the company’s GST number.
Explore other Pilz components
Compare safety relays
Browse electrical and industrial automation products
Frequently asked questions
1. Can 777538 be set to exactly 30 seconds?
No. This model has discrete settings, with 20 and 40 seconds on either side of 30 seconds. If the design requires exactly 30 seconds, evaluate article 777530 and validate the complete safety circuit before substitution.
2. Is a 60-second delay rated PL e?
No. The delayed outputs at 60 seconds fall in the PL c / Category 1 / SIL 1 group. The higher rating of the instantaneous contacts must not be assigned to the delayed circuit.
3. Can I use the NC contact as an additional safety output?
No. The 41–42 NC contact is intended for auxiliary signalling, not a safety function.
4. Can I connect a light curtain directly to this article?
Do not assume direct compatibility. The manual’s electronic light-guard connection example is limited to specified 24 V DC-only articles, not 777538. Check the sensor output type and approved interface with a qualified safety engineer.
5. Can all five NO safety contacts carry 8 A simultaneously?
No. The manual gives a 5 A conventional thermal current per contact when five contacts are loaded under AC1/DC1 conditions. Apply the separate utilisation-category rating and all installation limits.
6. What if the Ambattur order quantity exceeds available stock?
Indus MegaMart accepts orders and payment even when stock is insufficient or zero. Its standard policy is delivery within 7–14 days for quantities above available stock; confirm the actual commitment for your pincode before payment.
7. Are the P3/P4 and P5 terminal sets included?
Pilz identifies 374281 (P3+P4) and 374282 (P5+P5) as optional accessory sets. Confirm the supplied contents and selling unit before purchasing extra terminals.
Order Pilz PNOZ XV3.1P 777538 for delivery in Ambattur